Dwelling Unit Load Calculator

NEC 220 — Standard Method (Part III) vs. Optional Method (220.82), Compared
Light

Saved Projects ▸

Autosaved locally in this browser — use Export Project above for a portable .json backup
Unsaved project — this draft isn’t in Saved Projects. Save it to keep it as a named project.

Project Info

Dwelling & Circuit Inputs

Common to both methods — general lighting, small appliance, and laundry loads per 220.41 / 220.52
120/240 V, or 120/208 V from a 208Y system. One setting for the building — also shown under Multifamily Feeder Inputs.
1500 VA per circuit — 220.52(A)
1500 VA per circuit — 220.52(B). Set to 0 only where a common laundry facility is provided elsewhere on the premises for all occupants — 210.52(F) Exception No. 1.

Range & Dryer

Table 220.55 (ranges/cooking equip.) & Table 220.54 / 220.82(B) (dryer)
Enter each cooking appliance separately. Standard method (Table 220.55): appliances over 8¾ kW through 27 kW use Column C (each under 12 kW counted as 12 kW; +5% per kW or major fraction the average exceeds 12 kW — Notes 1 & 2). Appliances over 1¾ kW through 8¾ kW use Column A (under 3½ kW) or Column B (3½–8¾ kW) per Note 3, or Column C with the rest — whichever is lower. Appliances 1¾ kW or less, or over 27 kW, are outside the table and taken at 100%. Optional method: full nameplate kW sum, no table reduction — 220.82(B)(3).
Standard method: each dryer at the greater of nameplate or 5000 W, 100% demand — 220.54 / Table 220.54. Optional method and 220.84 feeder: nameplate rating — 220.82(B)(3), 220.84(C)(3). (Table 220.54's demand-factor reduction below 100% applies to the count of dwelling-unit dryers on a multi-unit feeder, not to multiple dryers within a single unit.)

Fixed / Fastened-in-Place Appliances

Water heater, dishwasher, disposal, microwave, compactor, etc. — 220.53
Standard method: if 4 or more fastened-in-place appliances rated ¼ hp / 500 W or greater (excluding cooking equipment, dryers, space heating, A/C, and EVSE), apply a 75% demand factor to those appliances' sum — 220.53. Appliances entered below 500 VA don't count toward the four and are carried at 100%. Optional method: all appliance nameplates included in the general 100%/40% demand block — 220.82(B)(4).

EV Charging Equipment

220.57 (standard) & 220.82(B) (optional — full nameplate, no 7200 VA floor)
Standard method: greater of 7200 VA or nameplate rating per unit, 100% demand, calculated separately from the fixed-appliance load — 220.57. Optional method: actual nameplate VA (the 7200 VA floor doesn't apply to the optional method) folded into the general 100%/40% block — 220.82(B). Not evaluated here: an EVEMS (Article 750) load-management system that could reduce this further.

Motor Loads

Well pump, sump pump, other dwelling-unit motors — 430.24
Sum of nameplate VA plus 25% of the largest single motor's nameplate VA — mirrors 430.24's rule for feeder/branch-circuit conductors supplying two or more motors. Standard method: added as its own line at 100% demand. Optional method: the same value is folded into the 220.82(B) general load, so it's subject to the 100%/40% demand factor.

Heating & Air Conditioning

220.60 (standard, noncoincident) & 220.82(C) (optional, largest applicable category)
Electric heating (resistance or heat pump) is subject to Article 220's heating demand factors (220.60 standard, 220.82(C) optional). A gas/oil/propane furnace has no electrical heating load to demand-factor — only its blower motor/controls draw current, so it's treated as a fixed connected load instead.
Standard method always uses 100% of the larger of heating or cooling (noncoincident loads, 220.60). Optional method uses 100% of A/C vs. the selected category's demand on the heating VA, and takes the larger of the two.

Optional Method Eligibility

220.82 applies only to a dwelling served by a single 100A+ service/feeder supplying that one dwelling unit

Results — Method Comparison

Both totals divided by service voltage for calculated load current

Standard Method

NEC 220 Part III
Total calculated load
— VA
Load current: —

Optional Method

NEC 220.82 — one-family dwelling
Total calculated load
— VA
Load current: —
—
Standard Method (NEC 220 Part III): General lighting at 220.41 (3 VA/sq ft, floor area per 220.11); small-appliance and laundry circuits (220.52) combined and demand-factored per Table 220.42(A) (100% of first 3000 VA, 35% of next 3001–120,000 VA, 25% of remainder); fastened-in-place appliances at 100% demand (75% on those rated ¼ hp / 500 W or more when there are 4 or more of them, per 220.53, excluding cooking equipment, dryers, EV charging equipment, motors, and space heating/AC); cooking appliances demand-factored per Table 220.55, each appliance counted individually (Column C with Notes 1–2 for appliances over 8¾ kW; Columns A/B per Note 3 for appliances over 1¾ kW through 8¾ kW, or Column C if lower; appliances 1¾ kW or less or over 27 kW at 100%); dryer(s) per Table 220.54 (100% each, 5000 W minimum); EV charging equipment at the greater of nameplate or 7200 VA each, 100% demand (220.57); motor loads at nameplate sum plus 25% of the largest motor (430.24); heating and air conditioning as noncoincident loads at 100% of the larger value (220.60).

Optional Method (220.82): Applies only when both eligibility checkboxes above are checked (single 100A-or-greater service/feeder, serving only this one dwelling unit) — otherwise the result is flagged not applicable. General loads (lighting, small appliance, laundry, all appliance/range/dryer/EV nameplates, and motor loads) demand-factored at 100% of the first 10 kVA plus 40% of the remainder (220.82(B)); heating/cooling load taken as the largest of the applicable categories in 220.82(C) — for a heat pump with supplemental heat, compressor at 100% plus supplemental heat at 65% (220.82(C)(3)).

Minimum Conductor & Service Size: Each method's calculated load current is rounded up to the nearest standard overcurrent device rating (240.6(A)), then matched to the smallest copper and aluminum/copper-clad aluminum conductor listed in Table 310.12 (120/240-volt and 120/208Y-volt, 3-wire, single-phase dwelling services and feeders) for that rating. Table 310.12 applies only to a single dwelling unit's service/feeder — a feeder serving multiple dwelling units, house/common loads, or non-dwelling loads must be sized from Table 310.16 instead, as must any load calculating above 400A.

Scope: This tool assists engineering judgment; verify occupancy classification, service eligibility for the optional method, and Table 220.55 range-demand notes against the NEC edition adopted by the Michigan Electrical Code for permit submittals.

Disclaimer: This tool is provided as a reference aid only and does not constitute engineering advice or a substitute for review, calculation, and sealing by a licensed Professional Engineer. Argento Engineering PLLC makes no warranty, express or implied, as to the accuracy or completeness of results produced by this tool, and assumes no liability for any loss, damage, injury, or claim arising from its use or misuse by any party, including third parties. All results must be independently verified against the applicable code edition and project-specific conditions before use in design, construction, or permitting.