Fire Pump Voltage Drop Calculator

NEC 695.7 / NFPA 20 §9.4 — Starting & Running Voltage Drop
Light

Saved Projects ▸

Autosaved locally in this browser — use Export Project above for a portable .json backup
Unsaved project — this draft isn’t in Saved Projects. Save it to keep it as a named project.

Project Info

Starting — controller line terminals (15% max)
—%
—
Running — controller load terminals (5% max)
—%
—

Motor & Load Data

Basis for both starting and running checks below
Interpolated by HP & voltage — preliminary only, verify against the actual motor/pump submittal nameplate FLA.
Added to starting current for worst-case controller line-terminal check.
Across-the-line uses the full locked-rotor current above for every starting-condition calculation below (starting voltage drop, disconnect/OCPD sizing, generator starting kVA). Soft start scales that same locked-rotor current down by a percentage reduction (Advanced Settings). Solid-state/VFD instead starts from near-zero frequency and voltage, so its starting current is modeled as a percentage of FLA (also set in Advanced Settings) rather than a reduced fraction of locked-rotor current.
Typical induction motor LRC PF ≈ 0.3–0.5 lagging.
Typical NEMA fire pump motor full-load PF ≈ 0.85–0.90.

Feeder Diagram

Source → feeder segment(s) → fire pump controller · click a value to edit it

Feeder — Utility Source to Controller

One physical feeder, evaluated at both starting and running current · NEC 695.7(A)/(B)
Same voltage basis used for both checks below — also editable directly on the diagram above, under the source symbol.

Segment 1

Results

Both checks below apply to the same feeder, summed across all active segments
Starting voltage drop
—%
Within limit
⏚ SourceController ▷
15%
0%
Current used: starting current per the selected starting method (Motor & Load Data) + jockey. Exception: the 15% limit does not apply to emergency-run mechanical starting (NEC 695.7(A) Exception).
Running voltage drop
—%
Within limit
⏚ SourceController ▷
5%
0%
Current used: 115% × motor FLA (NEC 695.7(B)).
NEC 695.6(B)(1) minimum conductor ampacity
Required ≥ 125% × (fire pump FLA + jockey FLA), checked independently against each segment's selected conductor.
Minimum conductor size finder
Holds every other segment fixed and steps up through the table (same material/method as the selected segment) to find the smallest size for that segment that brings starting VD ≤ 15%, running VD ≤ 5%, and 695.6(B)(1) ampacity all within limits at once.

Advanced Settings ▸

Conductor auto-sizing behavior, reduced-current starting method defaults