Arc Flash
Annex D + independentIEEE 1584-2018
- Reproduces every printed value in Annex D.1 (4.16 kV) and D.2 (480 V), including the reduced arcing current cases.
- Cross-checked on 2,800 cases against an independent open-source IEEE 1584 package, itself verified against Annex D and the official IEEE spreadsheet: all 5 electrode configurations, 208 V to 15 kV. Agreement to about 0.0002%.
- Matches SKM within about 0.1% on two test cases.
One-Line Studio
IndependentShort circuit · voltage drop · IEEE 519
- Fault current at every bus matches an independent textbook calculation on 1,200 random networks, to rounding error: utility, transformer and generator sources, single and three phase, parallel sets.
- Motor contribution uses a full-network solve, checked against an independent impedance-matrix solution on 400 networks.
- Voltage drop checked against an independent calculation; harmonic limit tables checked cell by cell against IEEE 519-2022.
- The references were deliberately broken to prove the tests catch errors.
Fire Pump Voltage Drop
IndependentNEC 695.7 · NFPA 20
- Starting and running drop match an independent exact (phasor) solution on 3,000 random feeders, including parallel sets, MI cable and single phase.
- Never reads below a model of the motor as its locked-rotor impedance, over 12,240 realistic starting cases.
- Step-down transformer impedance is included in the starting check, verified by hand calculation.
- Motor currents checked against NEC Tables 430.250 / 430.248, code letters against 430.7(B); 17,000+ checks.
Dwelling Unit Load
NEC Annex DNEC Article 220
- Matches every NEC Annex D dwelling example it computes: D1(a) standard method, D2(a)/(b)/(c) optional method (heating, A/C, heat pump), D4(a)/(b) multifamily per unit and feeders, D5(b) at 208Y/120 V, and the D6 range demands.
- Service conductor sizes match D7 for all 11 ratings from 100 to 400 A.
- 56 Annex D checks plus 50 hand calculations.
Duct Bank Heating
Independent + NEC tableNeher-McGrath · IEC 60287
- Matches an independent implementation (different solver) within 0.003 °C and 0.1% ampacity over 1,500 random banks.
- Compared with NEC Table 315.60(C)(11) over 120 cells; the grouping effect between 1, 3 and 6 ducts matches the table within about 4%.
On the table’s own basis the tool reads 0.6% to 8% above NEC Table 315.60(C)(11) (3.7% on average). Use the tool’s “NEC Table Basis” preset when comparing with the table.
Raceway Ampacity
NEC tables + hand calcsNEC 310.15 · Chapter 9
- Table values checked against the printed NEC 2023: 310.16, Chapter 9 Tables 4, 5 and 8, and 250.122.
- Derating, conduit fill, breaker and EGC sizing checked against hand calculations; 622 checks.
Cable Tray Ampacity
NEC tables + hand calcsNEC 392.80
- Table values checked against the printed NEC 2023: 310.16, 310.17, 310.20, Annex B Table B.2(3), 315.60(C) and the 392.22 fill tables.
- Every 392.80 case (touching, spaced single layer, triplexed, medium voltage) checked against hand calculations; 224 checks.
Not yet tested
GEC & Bonding Jumper, DTE Energy Transformer Fault Current and DTE Energy Meter Enclosure don’t have test suites yet.
Worked examplesWhere a standard prints its own examples (IEEE 1584 Annex D, NEC Annex D), the tool has to reproduce them.
Independent implementationsThe same method written separately, often with a different solver, compared over thousands of random cases.
Tests that can failReferences are deliberately broken to confirm the comparison would catch a real mistake.